Low suction pressure...

refrigeration maintenance

When I arri
ved the compressor was tripped off on its overload. Once cooled trouble shooting began. The compressor was found short cycling due to low suction pressure. The short cycling took out the pressure control and wore out the contactor. Both components were replaced. Cause for low suction pressure...

refrigeration maintenance

The evaporators grills were plugged with dust and debris
restricting airflow. The product was all ready pulled so we pressure washed the cases...

refrigeration maintenance

The filter driers had a
slight temperature drop across the them so we replaced them with a larger model of Sporlan. It was odd that all driers upstream of the TX valves had the same problem. We suspected the the drier off the receiver may have sent debris down the liquid line so we replaced that one aw well...

refrigeration maintenance

It was three in the
morning buy this time.

refrigeration maintenance

When we left there was a 2
0 degree coil TD across the evaporators...