System Accessories

Crankcase Pressure Regulator (CPR)

  • Valve operation CRO (close on a rise of outlet)

  • CROT --  has a pressure tap

  • Adjustment under cap (watch service manifold for pressure adjustment)

Purpose

  • To limit the amount of pressure to a low temperature compressor during hot pull down and defrost thus preventing compressor overloading

Location

  • In the suction line close to the compressor, downstream of any other accessory







Return to System Accessories

























6