Crankcase Pressure Regulator (CPR)
- Valve operation CRO (close on a rise of outlet)
- CROT -- has a pressure tap
- Adjustment under cap (watch service manifold for pressure adjustment)
Purpose
- To limit the amount of pressure to a low temperature compressor during hot pull down and defrost thus preventing compressor overloading
Location
- In the suction line close to the compressor, downstream of any other accessory
|