4

Refrigerant Piping

Hot Gas Line Design and Installation

    • Common goal: Limit Hot Gas Line pressure drop to 2 F (equivalent pressure drop)

Goals

  • Ensure oil leaving compressor travels to the condenser

  • Avoid trapping

  • Use proper vibration devices

  • Use noise dampening devices

  • Prevent refrigerant and oil from returning to the compressor during the off-cycle

  • Ensure a minimum gas velocity of 500 Fpm. for horizontal runs

  • Ensure a minimum gas velocity of 1000 Fpm. for vertical runs

  • A trap at the base of all hot gas risers over 8 ft. (good to 25 ft.)

  • Use double hot gas riser if system capacity can be reduced to 50% of full load
  • Ensure a max gas velocity of 4000 fpm. is not exceeded

  • Pitch all horizontal runs ½” per 10 ft. in the direction of flow

  • Avoid bull heading of common discharge

  • Result of bull heading….excessive noise, vibration, excessive pressure drops migration to the heads


    FOLLOW CODE REQUIREMENTS

Example of a Riser

Purpose of traps on the riser

  • Collect any oil on the riser during off cycle

  • As it starts back up oil is collected by high pressure refrigerant and atomizes

  • Above 25 ft. or more (DOUBLE TRAP)

  • Second trap is placed half way to the top

  • To collect extra oil (no slugging)

Example of a Double Riser and a Double Double Riser

Purpose of the inverted trap

  • Prevent oil going up secondary from dropping down primary (always on larger  diameter riser tube)

To Avoid Bull Heading (on common discharge)

  • Use tee as a y (y’s are very expensive)






Return to Refrigerant Piping

























6