Metering Devices

Low Load Limits


Both liquid distributors and TEV’s have low load Limitations

    Over sizing of devices will cause unequal distribution of refrigerant through the evaporator circuits at low loads

    The top of the evaporator circuits will begin to starve

    The bottom feeder will cause flooding to the compressor

    If this situation is found the size of the nozzle can be changes to smaller size

    The low load limits for most nozzles is about 50% of its capacity

    The low load limits for the TEV is 30% of its rated maximum cap.

     

 A TEV that is operating below its low load limit will cause HUNTING and it can be detected by:

    Taking a temperature measurement at the bulb and recording superheat readings for a certain amount of time

    Reading will be erratic and not constant

     

Double- Ported Expansion Valve

    This type of TEV allows connection of two separate evaporator circuits without the use of a distribution device

     

Liquid Distributors

    In order to provide equal refrigerant distribution through an evaporator with more than one circuit a liquid distributor is used

    Can have 2 to 40 lines depending on the size of the evaporator

    Always uses an externally equalized line because of pressure drop

    There is only one distributor per metering device

    Some liquid distributors use a thick flat washer inside the distributor (called a nozzle)

    It provides for pressure drop

    Better mixture of the liquid and gas

    Ensures equal mixture of the liquid and gas detection to all circuits

    They are inter changeable

     






Return to Metering Devices

























6