Shell and Tube Evaporator Types
|
Dry
- Location of primary refrigerant = tube side
- Location of secondary refrigerant = shell side
- Purpose of baffle (full or half) is to provide maximum exposure of secondary refrigerant to primary refrigerant circuit
|

|
Flooded
- Location of primary refrigerant = shell side
- Location of secondary refrigerant = tube side. Tube bundle in bottom of the shell in liquid refrigerant
- Purpose of eliminators to prevent liquid from returning to the compressor
|
|
Capacity or Efficiently Control
- constant water flow at all times
Temperatures
- Low temp Application 2 degrees F TD (Secondary Refrigerant Entering/leaving)
- High Temperature Applications 10 to 15 F TD (secondary Ref. Entering /leaving)
- Air conditioning chilled water supply at 40 to 45 F
- Air conditioning supply air temp. 55 F
Secondary refrigerant Controlled by Entering Condition
- When evacuating system of primary ref.
- Must circulate secondary pump for secondary ref or it will freeze the whole system
|